tM-7530

ICP DAS has provided a lot of UART/CAN product solutions which are widely recommended in the market. These UART/CAN converters can help users to implement the communication between RS-232 and CAN network. In order to cater for costing requirement, we provide a new solution of RS-232/CAN converter-tM-7530. The tM-7530 is a tiny RS-232/CAN to fit narrower environment as a result of its small size. It has isolation on power side and on CAN bus side and its performance is faster than other RS-232/CAN module. The function of tM-7530 can full compatibly with I-7530 and I-7530T. Besides, it provides new function such as listen only. User can use this function to listen CAN bus messages and error detection. According to above features, tM-7530 is an economical and practical RS-232/CAN converter solution.

 

 

Request For Quotation

    Description

    Moreover, we expand the functionalities of tM-7530 for some special application. In pair connection mode, tM-7530 can be used to connect PC with other RS-232 devices at the same time. The application architecture may be as follows.

    Applications

     

    • Control System
    • Building Automation
    • Factory Automation
    • Distributed data acquisition

     

     

     

    Features

    • Compatible with CAN specification 2.0A and 2.0B
    • Fully compatible with ISO 11898-2 standard
    • Support various CAN baud rate from 10K bps to 1M bps
    • Support user-defined CAN baud rate
    • Support various RS-232 baud rate from 110 bps to 230400 bps
    • External option 120 Ω terminal resistor
    • Software configurable CAN and RS-232 communication parameters
    • Power, data flow and error indicator for CAN and RS-232
    • Watchdog inside
    • Support pair connection mode
    • Software buffer on CAN bus side and RS-232 side
    • Support user-defined end of characters on pair connection mode
    • Support listen only mode
    • Support time stamp response on RS-232 side

     

    Utility

    Software Utility Features

    • CAN bus baud rate configuration
    • CAN bus acceptance filter configuration
    • CAN 2.0A or CAN 2.0B specific selection
    • RS-232 baud rate and data format configuration
    • Communication mode(normal , pair connection , and listen only mode ) configuration
    • Easy test to transmit/receive CAN messages
    • CAN bus data flow detection
    • Group Send CAN messages for special application
    • Trigger event setting for advance received CAN messages
    • Integrate all CAN bus converter utility of ICP DAS
    Software

     

    Hardware Specifications

    CAN Interface
    Transceiver NXP TJA1042
    Channel number 1
    Connector Spring type connector
    Baud Rate (bps) 10 k, 20 k, 50 k, 100k, 125 k, 250 k, 500 k, 800 k, 1 Mbps (allow user-defined CAN baud rate)
    Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
    Terminal Resistor External option terminal resistor
    Specification ISO-11898-2, CAN 2.0A and CAN 2.0B
    RS-232 Interface
    Connector 9-pin female D-Sub (TxD, RxD, GND, N/A for others)
    Baud Rate (bps) 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400
    Data bit 5, 6, 7, 8
    Stop bit 1, 2
    Parity bit None, Even, Odd
    LED
    Round LED ON LED: Power and Data Flow; ERR LED: Error Status
    Power
    Protection Power reverse polarity protection, Over-voltage brown-out protection
    Power Consumption 1W
    Mechanism
    Installation DIN-Rail
    Dimensions 52mm x 86mm x 32mm (W x L x H)
    Environment
    Operating Temp. -25 ~ 75 ℃
    Storage Temp. -30 ~ 80 ℃
    Humidity 10 ~ 90% RH, non-condensing

    Hardware Structure

    Wire Connection

    Pin Assignment

    Pin 3-wire RS-232
    1 N/A
    2 RS-232 TxD
    3 RS-232 RxD
    4 N/A
    5 RS-232 GND
    6 N/A
    7 N/A
    8 N/A
    9 N/A
    Pin Power
    1 +Vs
    2 GND
    3 F.G.
    Pin CAN
    1 CAN_L
    2 CAN_H
    3 CAN_GND

     

    Performance Test

    Performance test: from CAN to RS-232(115200, n, 8, 1). Unit: Frames Per Second(FPS).
    Baud rate 1000K 800K 500K 250K 125K 50K 20K 10K
    CAN 2.0A 519 519 523 522 522 416 176 88
    CAN 2.0B 423 423 426 425 426 353 146 74
    Performance test: from RS-232(115200, n, 8, 1) to CAN. Unit: Frames Per Second(FPS).
    Baud rate 1000K 800K 500K 250K 125K 50K 20K 10K
    CAN 2.0A 523 524 523 522 520 451 180 90
    CAN 2.0B 425 426 427 426 427 377 150 75

    Ordering Informations

    tM-7530 CR
    Intelligent tiny RS-232/CAN converter (RoHS)

    Datasheet

    tM-7530

    CAN_Converter_usermanual_eng_v1.4

    tM-7530_quickstart_en_v1.0.0