I-7530 I-7530T I-7530FT

CAN (Controller Area Network) is a serial bus system especially suited to structure intelligent industry devices networks and build smart automatic control systems. The following figure shows the application architecture for I-7530/I-7530T/I-7530FT modules. The PC can be the CAN host, monitor or HMI to access/control the CAN device through the CAN network by the I-7530/I-7530T/I-7530FT Converters. The programmable RS-232 device (For example: I-8411/I-8431/I-8811/I-8831/W-8031/W-8331/W-8731 embedded controller) can use the serial port to connect to the CAN network via the I-7530/I-7530T/I-7530FT modules. In order to use the CAN network with traditional RS-232 devices, we provide a way to achieve this purpose. The I-7530/I-7530T/I-7530FT are designed to unleash the power of CAN bus via RS-232 communication method. It accurately converts messages between CAN and RS-232 networks. This module let you to communicate with CAN devices easily from any PC or devices with RS-232 interface.

 

Request For Quotation

    Description

    CAN (Controller Area Network) is a serial bus system especially suited to structure intelligent industry devices networks and build smart automatic control systems. The following figure shows the application architecture for I-7530/I-7530T/I-7530FT modules. The PC can be the CAN host, monitor or HMI to access/control the CAN device through the CAN network by the I-7530/I-7530T/I-7530FT Converters. The programmable RS-232 device (For example: I-8411/I-8431/I-8811/I-8831/W-8031/W-8331/W-8731 embedded controller) can use the serial port to connect to the CAN network via the I-7530/I-7530T/I-7530FT modules. In order to use the CAN network with traditional RS-232 devices, we provide a way to achieve this purpose. The I-7530/I-7530T/I-7530FT are designed to unleash the power of CAN bus via RS-232 communication method. It accurately converts messages between CAN and RS-232 networks. This module let you to communicate with CAN devices easily from any PC or devices with RS-232 interface.

    Moreover, we expand the functionalities of I-7530/I-7530T/I-7530FT for some special application. In pair connection mode, I-7530/I-7530T/I-7530FT can be used to connect PC with other RS-232 devices at the same time. The application architecture may be as follows.

    3000V isolation on CAN side (for I-7530/I-7530T)
    The CAN port of I-7530/I-7530T is an isolated with 3000V isolation. This isolation can protect the local RS-232 devices from the damage signal coming from CAN network.

    Watchdog inside
    The watchdog is a hardware reset circuit to monitor the operation status. When working in harsh or noisy environment, the I-7530/I-7530T/I-7530FT may shut down by the external signal. The circuit may let the I-7530/I-7530T/I-7530FT to work continuously and never halt.

    Power and Error indicator display
    There are two indicators on the I-7530/I-7530T/I-7530FT.The power indicator can help user to check whether the I-7530/I-7530T/I-7530FT is standby or transmitting/receiving messages. The Error indicator will be turned on when some errors occur on the I-7530/I-7530T/I-7530FT.

    Applications

    • Control System
    • Building Automation
    • Factory Automation
    • Distributed data acquisition

    Features

    • Compatible with CAN specification 2.0A and 2.0B
    • Fully compatible with ISO 11898-2 standard (for I-7530/I-7530T)
    • Fully compatible with ISO 11898-3 standard (low speed fault tolerance) (for I-7530-FT)
    • Support various baud rate from 10K bps to 1M bps
    • Jumper for 120 Ω terminal resistor (for I-7530/I-7530T)
    • Software configurable CAN and RS-232 communication parameters
    • Power, data flow and error indicator for CAN and RS-232
    • Watchdog inside
    • Support transparent communication mode
    • 1000 frames in CAN received buffer and 900 frames in RS-232 received buffer
    • Full-duplex communication mode of RS-232 devices is not supported

    Additional Information

    Software Utility Features
    • CAN bus Baud rate configuration
    • CAN acceptance filter configuration
    • CAN 2.0A or 2.0B specific selection
    • RS-232 Baud rate and data bit setting
    • RS-232 responded selection
    • Easy test to transmit/receive can messages
    • Setting for I-7530/I-7530T/I-7530FT communication mode (normal mode or pair connection mode)
    CAN Monitor & Datalog Tool
    • It has a CAN message field which can display the receiving CAN messages in
    • Decimal or HEX mode
    • Can display the timestamp of each received CAN message
    • Users can change the display mode, up-down, down-up or stop
    • It can count the number of received CAN messages
    • Data Log : It can save the CAN message as “ txt ” file
    • Has CAN ID filter function
    • Can send CAN message to CAN BUS according the defined interval time

    Hardware Specifications

    Item
    I-7530
    I-7530T
    I-7530-FT
    Hardware
    EEPROM
    2 KB (for system information), 100,000 erase/write cycles
    CAN Interface
    Transceiver
    NXP 82C250
    NXP TJA1042
    AMIS 41682
    Channel number
    1
    Connector
    9-pin male D-Sub (CAN_L, CAN_H, N/A for others)
    Baud Rate (bps)
    10 k, 20 k, 50 k, 125 k, 250 k, 500 k, 800 k, 1 Mbps
    (allow user-defined CAN baud rate)
    10 k, 20 k, 50 k, 125 k (allow user-defined CAN baud rate)
    Isolation
    3000 VDC for DC-to-DC,
    2500 Vrms for photo-couple
    NONE
    Terminal Resistor
    Selectable 120Ω terminal resistor by jumper
    1 kΩ for CAN_H and CAN_L
    Specification
    ISO-11898-2, CAN 2.0A and CAN 2.0B
    ISO-11898-3 (low speed fault tolerance), CAN 2.0A and CAN 2.0B
    Receive Buffer
    1000 data frames
    RS-232 Interface
    Connector
    9-pin female D-Sub (TxD, RxD, GND, N/A for others )
    Baud Rate (bps)
    110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps
    Data bit
    5, 6, 7, 8
    Stop bit
    1, 2
    Parity bit
    None, Even, Odd
    Receive Buffer
    900 data frames
    LED
    Round LED
    ON LED: Power and Data Flow; ERR LED: Error Status
    Power
    Protection
    Power reverse polarity protection, Over-voltage brown-out protection
    Power Consumption
    1 W
    Mechanism
    Installation
    DIN-Rail
    Dimensions
    72mm x 118mm x 33mm (W x L x H)
    Environment
    Operating Temp.
    -25 ~ 75 ℃
    Storage Temp.
    -30 ~ 80 ℃
    Humidity
    10 ~ 90% RH, non-condensing

    Hardware Structure

    Wire Connection

     

    Pin Assignment

     

    Internal I/O Structure

    Performance Test

    The test is the performance which transfer 8 bytes data frame from CAN to RS232. (for I-7530/I-7530T)
    CAN setting
    Transfer frames
    Transfer time(ms)
    RS-232 setting
    Receive frames
    Receive time (ms)
    The max frames/sec
    Data<8 byes/frme
    RS232 command length
    2.0A 1Mbps
    1,000
    200
    115200,n,8,1
    1,000
    2954
    338
    >=338
    22 B
    2.0A 1Mbps
    1,000
    200
    115200,n,7,1
    1,000
    2775
    360
    >=360
    22 B
    2.0B 1Mbps
    1,000
    200
    115200,n,8,1
    1,000
    3580
    279
    >=279
    27 B
    2.0B 1Mbps
    1,000
    200
    115200,n,7,1
    1,000
    3337
    299
    >=299
    27 B

     

    The test is the performance which transfer 8 bytes data frame from RS232 to CAN. (for I-7530/I-7530T)
    CAN setting
    Transfer frames
    Transfer time (ms)
    RS-232 setting
    Receive frames
    Receive time (ms)
    The max frames/sec
    Data<8 byes/frame
    RS232 command length
    2.0A 1Mbps
    1,000,000
    2,612,243
    115200,n,8,1
    1,000,000
    2,612,243
    382
    >=382
    22 B
    2.0A 1Mbps
    1,000,000
    2,441,130
    115200,n,7,1
    1,000,000
    2,441,130
    409
    >=409
    22 B
    2.0B 1Mbps
    1,000,000
    3,142,043
    115200,n,8,1
    1,000,000
    3,142,043
    318
    >=318
    27 B
    2.0B 1Mbps
    1,000,000
    3,142,043
    115200,n,7,1
    1,000,000
    2,966,646
    337
    >=337
    27 B

    Ordering Informations

    I-7530-G
    Intelligent RS-232 to CAN converter
    I-7530-G CR
    Intelligent RS-232 to CAN converter (RoHS)
    I-7530T-G CR
    Intelligent RS-232 to CAN converter (RoHS)
    I-7530-FT
    Intelligent RS-232/CAN low speed fault tolerant converter
    I-7530-FT CR
    Intelligent RS-232/CAN low speed fault tolerant converter (RoHS)

    Datasheet

    I-7530datasheet

    CAN_Converter_users_manual_en_v1.3

    i7530ft_quickstart

    i7530_quickstart